Skip to content

Notification Groups & Tones

A notification group defines how an alarm sounds, lights up, and repeats. Monitor items, custom APIs, and Modbus commands all reference the same group configuration.

Open Settings → Notifications. The table lists every group.

ColumnDescription
NameGroup name; the default group is named “Default”
LED styleNone, spin, flash, steady, pulse, or lit (depends on the LED model)
LED layersShown for stacked-light models
LED colorShown for full-color models; each layer can have its own color
DurationLight duration; 0 means the light follows the sound
VoiceWhether to speak the alarm
EmailWhether to send an email
ActionsView, edit, delete
  1. Click Add.
  2. Enter a name (2–16 characters, unique).
  3. Configure broadcast rules and light style.
  4. Click OK.
ParameterDescription
TonePrefix tone played before speech; choose “Off” or a tone
Repeat count0 no repeat; 1–9998 fixed repeats; 9999 infinite
IntervalMinutes between repeats, 1–1440
Light duration0–60 seconds; 0 means the light follows the sound. Must be greater than 0 when both tone and voice are off
VoiceSpeak the alarm text
Unacknowledged reminderKeep reminding while the alarm is unacknowledged

Options depend on the LED model:

Full-color LED: 0 none, 15 spin, 20 flash, 25 steady, 30 pulse.

Stacked light: 0 none, 40 lit (choose the layer count).

Full-color models can set one overall color or enable multi-layer colors. Stacked lights can select which layers to light.

  1. Enable quiet hours.
  2. Select weekdays.
  3. Set start and end times in 15-minute steps.
  4. Overlapping periods on the same day are merged.

Alarms are still recorded during quiet hours but produce no sound or light; broadcasting resumes afterwards.

Enable Email and enter recipients. The device uses the SMTP server configured under Settings → General → Mail server. Email quiet hours can be configured separately.

Click Test broadcast at the bottom of the edit dialog. The device plays the tone, speech, and light using the current group settings. Tests are not written to the broadcast log.

Click Delete and confirm. Monitor items that reference the group fall back to the default group. The default group cannot be deleted or renamed.

Tones are managed under Settings → General → Sound. Notification groups and APIs reference tones by number.

RangeTypeTestRenameDelete
0–99Built-inYesNoNo
100–149CustomYesYesYes
  1. Click upload and choose a file.
  2. Supported formats are wav and mp3, up to 5 MB each.
  3. Up to 50 custom tones are allowed, numbered 100–149 automatically.
  4. After upload, preview or rename the tone in the list.
  • Click Rename, enter a new name, and save.
  • Click Delete and confirm; the file is removed from the device.
  • Built-in tones can only be previewed.

When do group changes take effect? Immediately after saving. The current broadcast is unaffected; the next alarm uses the new settings.

Why does an alarm light up but stay silent? Check the voice switch, tone, and light duration. When both tone and voice are off, light duration must be greater than 0.

Why is a monitor item silent after deleting its group? The item has fallen back to the default group. Check the default group’s voice and tone settings.