Notification Groups & Tones
A notification group defines how an alarm sounds, lights up, and repeats. Monitor items, custom APIs, and Modbus commands all reference the same group configuration.
Notification Groups
Section titled "Notification Groups"Open Settings → Notifications. The table lists every group.
| Column | Description |
|---|---|
| Name | Group name; the default group is named “Default” |
| LED style | None, spin, flash, steady, pulse, or lit (depends on the LED model) |
| LED layers | Shown for stacked-light models |
| LED color | Shown for full-color models; each layer can have its own color |
| Duration | Light duration; 0 means the light follows the sound |
| Voice | Whether to speak the alarm |
| Whether to send an email | |
| Actions | View, edit, delete |
Create a Group
Section titled "Create a Group"- Click
Add. - Enter a name (2–16 characters, unique).
- Configure broadcast rules and light style.
- Click
OK.
Broadcast Rules
Section titled "Broadcast Rules"| Parameter | Description |
|---|---|
| Tone | Prefix tone played before speech; choose “Off” or a tone |
| Repeat count | 0 no repeat; 1–9998 fixed repeats; 9999 infinite |
| Interval | Minutes between repeats, 1–1440 |
| Light duration | 0–60 seconds; 0 means the light follows the sound. Must be greater than 0 when both tone and voice are off |
| Voice | Speak the alarm text |
| Unacknowledged reminder | Keep reminding while the alarm is unacknowledged |
LED Style
Section titled "LED Style"Options depend on the LED model:
Full-color LED: 0 none, 15 spin, 20 flash, 25 steady, 30 pulse.
Stacked light: 0 none, 40 lit (choose the layer count).
Full-color models can set one overall color or enable multi-layer colors. Stacked lights can select which layers to light.
Quiet Hours
Section titled "Quiet Hours"- Enable quiet hours.
- Select weekdays.
- Set start and end times in 15-minute steps.
- Overlapping periods on the same day are merged.
Alarms are still recorded during quiet hours but produce no sound or light; broadcasting resumes afterwards.
Email Notification
Section titled "Email Notification"Enable Email and enter recipients. The device uses the SMTP server configured under Settings → General → Mail server. Email quiet hours can be configured separately.
Broadcast Test
Section titled "Broadcast Test"Click Test broadcast at the bottom of the edit dialog. The device plays the tone, speech, and light using the current group settings. Tests are not written to the broadcast log.
Delete a Group
Section titled "Delete a Group"Click Delete and confirm. Monitor items that reference the group fall back to the default group. The default group cannot be deleted or renamed.
Tones are managed under Settings → General → Sound. Notification groups and APIs reference tones by number.
Tone Numbers
Section titled "Tone Numbers"| Range | Type | Test | Rename | Delete |
|---|---|---|---|---|
| 0–99 | Built-in | Yes | No | No |
| 100–149 | Custom | Yes | Yes | Yes |
Upload a Tone
Section titled "Upload a Tone"- Click upload and choose a file.
- Supported formats are
wavandmp3, up to 5 MB each. - Up to 50 custom tones are allowed, numbered 100–149 automatically.
- After upload, preview or rename the tone in the list.
Rename and Delete
Section titled "Rename and Delete"- Click
Rename, enter a new name, and save. - Click
Deleteand confirm; the file is removed from the device. - Built-in tones can only be previewed.
When do group changes take effect? Immediately after saving. The current broadcast is unaffected; the next alarm uses the new settings.
Why does an alarm light up but stay silent? Check the voice switch, tone, and light duration. When both tone and voice are off, light duration must be greater than 0.
Why is a monitor item silent after deleting its group? The item has fallen back to the default group. Check the default group’s voice and tone settings.