Skip to content

Home & Alarm Queue

The home page opens after login. It shows device status, monitoring and alarm statistics, and provides daily operations such as acknowledging, deleting, and clearing alarms. Data refreshes every 5 seconds.

The top bar shows CPU temperature, CPU usage, disk usage, and memory usage. Hover over disk or memory to see used and total capacity.

MetricDescription
CPU temperatureDegrees Celsius; the dot turns orange or red at higher temperatures
CPU usagePercentage
DiskUsed percentage; hover for used/total
MemoryUsed percentage; hover for used/total

With the monitor license, four cards are shown:

CardMeaning
Monitored hostsHosts with at least one enabled monitor item
Monitor pointsTotal enabled monitor items
Current alarmsAll records in the current alarm table
Unacknowledged alarmsAlarms still in the unacknowledged state

The table aggregates active monitoring, email, SNMP Trap, local network, API periodic broadcasts, and infinite loop broadcasts.

ColumnDescription
SelectionUsed for batch acknowledge or delete
ExpandShows event ID, notification group, repeated/maximum count, interval, and next broadcast time
HostAlarm source host; API broadcasts show the request source
MonitorMonitor item name; API broadcasts show “Periodic broadcast” or “Infinite broadcast”
MessageAlarm details or broadcast text
TimeWhen the alarm was first raised
StateUnacknowledged, acknowledged, periodic running/finished, infinite running
ActionsAcknowledge, unacknowledge, delay, delete
StateDescription
UnacknowledgedNew alarm not yet acknowledged
AcknowledgedAlarm acknowledged by an operator
Periodic runningAPI periodic broadcast has not reached its repeat count
Periodic finishedPeriodic broadcast completed all repeats
Infinite runningBroadcast from a notification group with repeat count 9999
  1. Select Acknowledge in the row action list to mark the alarm as acknowledged.
  2. Select Unacknowledge to return it to the unacknowledged state.

For normal alarms, the following delays are available: 10 minutes, 30 minutes, 1 hour, 6 hours, and 1 day. Delaying only changes the next broadcast time; it does not delete the alarm.

  • Normal alarms can be deleted with Delete alarm and confirmation.
  • Periodic and infinite broadcasts only show Delete, which also removes them from the broadcast queue.
  • Alarms generated by active monitoring cannot be deleted manually; they end when the monitor recovers.
  1. Select the alarms to process.
  2. Click the batch acknowledge icon and confirm.
  3. Click the batch delete icon and confirm.
  4. If no row is selected, the page asks you to select rows first and sends no request.
ButtonDescription
View queued broadcastsShows the current queue length, excluding the item being played
Delete all alarmsClears periodic broadcasts, infinite broadcasts, and the pending queue immediately
Skip current broadcastStops the current broadcast and continues with the next item

Without the monitoring license, the bottom of the page shows the latest 10 broadcast records: ID, broadcast text, duration, and time.

Selection and expanded rows disappear after refresh? The page refreshes every 5 seconds and restores selected and expanded rows automatically.

Why do monitoring alarms return after “Delete all alarms”? The action clears the broadcast queue and API broadcasts only. Active monitoring alarms reappear while the fault persists.

Why does an alarm stay unacknowledged? Acknowledging only changes the manual handling state. It does not stop repeat broadcasts; adjust the notification group or delete the loop broadcast instead.