Modbus TCP

Modbus TCP is designed for PLC and SCADA software scenarios, supporting template ID triggering and multi-register custom broadcasting.

The device supports pushing alarm information and common alarm control capabilities via the Modbus TCP protocol, applicable in industrial settings for interfacing with various PLCs, industrial automation equipment, etc.

  • Push alarm information (equivalent to Basic Features)
  • Trigger a preset voice alarm by specifying an ID
  • Query the current alarm queue count
  • Skip the current alarm
  • Clear the broadcast queue
  • Command templates

Simply configure the broadcast template and its corresponding ID in the interface, then pass the corresponding ID to trigger broadcasting.

To broadcast, you only need to write the preset corresponding ID to register 100 to trigger a voice broadcast. No voice encoding is needed on the sending side, greatly reducing integration effort. Below is an introduction to this feature. See Address Table

Parameter Description

  • Register Value: The value that triggers the alarm light to alert
  • Broadcast Content: When this command is triggered, the alarm light will voice broadcast the custom broadcast content
  • Notification Group: When the command is triggered, the alarm light will change according to the selected notification group

Notes

  • The port number in Modbus TCP configuration supports customization
  • Register values must not consist of a single 0 or start with 0. For example, if the value is 0x000a, the correct input should be a

Add the following rule in the rule table

Register value: a

Alarm content: Device temperature exceeds threshold, please check

Notification group: Default

The resulting data structure is as follows. Writing 0x000a to address 100 will trigger a voice alarm

Device temperature exceeds threshold, please check

A powerful broadcasting method that allows customizing light styles, colors, and broadcast content, but constructing data is relatively complex, implemented using multiple register writes.

Currently, all functions are implemented in Holding Registers, i.e., Holding Register registers, hereinafter referred to as HR registers.

Do not operate any registers other than HR registers.

LED style: 15

LED color array: ['#8a2be2']

Broadcast duration: 0

Alert tone: 001

TTS speed: 0

LED style parameters: [0.03,1]

Voice broadcast content: Welcome

The resulting data structure is as follows

[‘0x000f’, ‘0x008a’, ‘0x2be2’, ‘0x0000’, ‘0x0000’, ‘0x0000’, ‘0x0000’, ‘0x0000’, ‘0x0000’, ‘0x0000’, ‘0x0001’, ‘0x0000’, ‘0x0301’, ‘0x0000’, ‘0x0000’, ‘0x00e6’, ‘0xaca2’, ‘0x00e8’, ‘0xbf8e’, ‘0x00e4’, ‘0xbdbf’, ‘0x00e7’, ‘0x94a8’]

Use the write multiple registers command, starting from address 101, to push the broadcast.

Notes

  • When writing to the function bit area, the broadcast function area will not take effect even if data is written
  • Performing a read operation will trigger the device to update the status area data
  • Multiple flag bits in the function bit area can be used simultaneously and will all take effect
  • When Busy is 1, the data read from the status bits may be inaccurate. Please perform operations when the Busy bit is 0
  • Since the Modbus write multiple registers command can write a maximum of 123 registers at once, this is why the broadcast address ends at 223. 101-223 is exactly the maximum number of registers supported by a single write command.

Project files for the Modbus Poll tool are provided, along with a Python script for sending alarms via Modbus TCP.

Official Website - Resources - Boling Modbus TCP Protocol Debug Demo

Read/Write Permissions

  • Registers 40001-40060 are read-only
  • Registers 40080-40223 are read/write
  • Read commands are supported
  • Write single register and write multiple register commands are supported (i.e., function codes 0x06 and 0x10)

Address Range Allocation

  • Addresses 1-2 display system status, read-only
  • Addresses 80-81 are function bits, when function bits contain non-zero data, the broadcast function will not take effect
  • Address 100 is for Method 1 - Command Template
  • Addresses 101-223 are for Method 2 - Custom Broadcast

The following addresses default to the holding register address range. Address 1 in the table represents actual register address 40001.

Address (DEC) Function Example Notes
Status Area - Read Only
1 Register Data Processing Busy 0x0001 1 indicates processing, 0 indicates idle
2 Pending Broadcast Queue Count 0x0000
3~79 Reserved, Unused 0x0000
Control Function Area - Read/Write Supports Write Single and Multiple Register Operations
80 Skip Current Broadcast 0x0001 When set to 1, immediately proceeds to the next broadcast.
The system will automatically reset this register to 0 after the value is set.
81 Clear Broadcast Queue 0x0001 When set to 1, immediately clears the pending broadcast queue.
The system will automatically reset this register to 0 after the value is set.
82~98 Reserved, Unused 0x0000
Template Broadcast Function Area - Read/Write Supports Write Single and Multiple Register Operations
99 or 550-599 Delete periodic or infinite loop broadcasts created by template commands 0x0001 Specify the template ID for which to delete periodic or infinite loop broadcasts
100 or 500-549 Template ID 0x0001 Can be invoked by matching the ID in the Modbus template configuration interface. If the repeat broadcast option is configured, it will automatically create repeated broadcasts
Custom Broadcast Function Area - Read/Write Only Supports Multiple Register Operations
101 LED Style 0x0015 See [LED Style Parameters](/model-q/en/once-api/#led-style-parameters) in the Regular API
102 LED Color 1 - High 8 bits 0x00FF For example, if the color is `#22ffcc`, the value here is `0x0022`
103 LED Color 1 - Low 16 bits 0xccbb For example, if the color is `#22ffcc`, the value here is `0xffcc`
104 LED Color 2 - High 8 bits 0x00FF Color assignment method is the same as above. If multi-color is not needed, set to 0.
105 LED Color 2 - Low 16 bits 0xccbb Color assignment method is the same as above. If multi-color is not needed, set to 0.
106 LED Color 3 - High 8 bits 0x00FF Same as above
107 LED Color 3 - Low 16 bits 0xccbb Same as above
108 LED Color 4 - High 8 bits 0x00FF Same as above
109 LED Color 4 - Low 16 bits 0xccbb Same as above
110 Broadcast Duration 0x0015 Set broadcast duration, function equivalent to [Regular API - Constructing Request - play_time Parameter](/model-q/en/once-api/#interface-configuration)
111 Ringtone Number 0x0014 Set ringtone number, function equivalent to [Regular API - Constructing Request - tone Parameter](/model-q/en/once-api/#interface-configuration)
`0xFFFF` means no ringtone is used
112 TTS Speed 0x0000 Set TTS speed, function equivalent to [Regular API - Constructing Request - tts_speed Parameter](/model-q/en/once-api/#interface-configuration)
113 LED Style Parameters 0x0301 Only effective when LED style parameter is 15 or 20.
When LED style is `15`, `high 8 bits` * 0.01 = `led_style[0]`, low 8 bits = `led_style[1]`.
For example: [0.03, 1] corresponds to `0x0301`.
When LED style is `20`, `high 8 bits` * 0.1 = `led_style[0]`, `low 8 bits` * 0.1 = `led_style[1]`
For example: [1, 1] corresponds to `0x1010`.
114-115 Reserved, Unused 0x0000
116 Text Character 1 - High 8 bits 0x00e4 Each character occupies 2 registers, using UTF-8 encoding.
For example, the character `你` has UTF-8 encoding `e4bda0`, so register 116 stores the high 8 bits of the UTF-8 encoding, i.e., `0x00e4`
Register 117 stores the low 16 bits of the UTF-8 encoding, i.e., `0xbda0`. The following registers follow the same pattern.
117 Text Character 1 - Low 16 bits 0xbda0
118 Text Character 2 - High 8 bits 0x00e5 Each character occupies 2 registers, using UTF-8 encoding.
For example, the character `好` has UTF-8 encoding `e5a5bd`, so register 118 stores the high 8 bits of the UTF-8 encoding, i.e., `0x00e5`
Register 119 stores the low 16 bits of the UTF-8 encoding, i.e., `0xa5bd`. The following registers follow the same pattern.
119 Text Character 2 - Low 16 bits 0xa5bd
The following addresses until the end address are all text encoding content, following the same pattern.
223 Text Character 54 - Low 16 bits 0x0000